Frequency Dependences of leakage currents flowing through ZnO surge arrester block

ZnO 피뢰기 소자에 흐르는 누설전류의 주파수의존성

  • Published : 2005.05.13

Abstract

This paper presents the frequency-dependent characteristics of leakage currents flowing through ZnO surge arrester block. The leakage current-voltage (I-V) characteristic curves of the commercial ZnO surge arrester blocks were measured. The resistive leakage current was found to increase with increasing frequency in the low conduction region. The capacitance of ZnO block was independent of the magnitude and frequency of the applied voltage. The power losses of ZnO block increase as the frequency of applied voltage increases, because of the dielectric loss related to the frequency of the test voltage.

Keywords