Potential Ruse as a function of the Buried Depth for Structure

구조체의 매설깊이에 따른 전위상승

  • Gil, Hyoung-Jun (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Kim, Dong-Ook (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Kim, Dong-Woo (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Lee, Ki-Yeon (Electrical Safety Research Institute, subsidiary of KESCO) ;
  • Kim, Hyang-Kon (Electrical Safety Research Institute, subsidiary of KESCO)
  • 길형준 (한국전기안전공사 전기안전연구원) ;
  • 김동욱 (한국전기안전공사 전기안전연구원) ;
  • 김동우 (한국전기안전공사 전기안전연구원) ;
  • 이기연 (한국전기안전공사 전기안전연구원) ;
  • 김향곤 (한국전기안전공사 전기안전연구원)
  • Published : 2006.07.12

Abstract

This paper deals with an approach to the reduction of potential rise according to the buried depth of structure. In order to analyze the surface potential rise of structure, an electrolytic tank which simulates the semi-infinite earth has been used. The potential rise has been measured and analyzed for types of structure using an electrolytic tank experimental apparatus in real time. The structure models were designed through reducing real buildings and fabricated with two types on a scale of one-one hundred sixty When a test current flowed through structure models, the potential rise of outline frame type(structure model A) was more high than that of electric cage type(structure model B). The distributions of surface potential rise are dependent on the buried depth of structure model.

Keywords