Study of the Electric Shock Risk in Water at the Waterpark, Public Bath
물놀이.입욕시설에서의 수중 감전 위험성 연구
- Kim, Chong-Min (Electrical Safety Research Institute KESCO) ;
- Kim, Han-Sang (Electrical Safety Research Institute KESCO) ;
- Kim, Gi-Hyun (Electrical Safety Research Institute KESCO)
- Published : 2006.07.12
Abstract
This paper presents the evaluation electric shock risk in water so that we made and designed a bathtub which is the same size in real public bath. and then we did an experiment, provided of electric leakage in various conditions so, we measured how to form an electric gradient and knew the electric gradient is formed variously under exposed conductor in water. also we made certain that electric shock risk is down if we insert an insulated pipe in bathtub pipe which is prevent from being formed the electric field sharply.