MV급 케이블 중간접속부의 PD 측정을 위한 UHF-센서와 HFCT-센서의 비교시험

Comparison test for PD measuring about UHF-sensor and HFCT-sensor in cable joint-box of MV grade

  • 발행 : 2006.07.12

초록

In this paper, we measured PD signals from artificial surface defects and corona discharges under laboratory circumstances like the fields using both HFCT-sensor and UHF-sensor for MV grade XLPE cable with AMP, spectrum analyzer and oscilloscope. Also, detected signals were analyzed via PRPDA system in this paper. As a result, in this case of HFCT-sensor, the amount of background noise are larger than as compared to UHF-sensor. There is needed some hardware or software or software algorithm removing background noise effectively for diagnosis the underground power transmission cable in the case of HFCT-sensor.