Operational Characteristics in integrated Three-Phase a Flux-Lock type SFCL according to Fault Conditions

3상 일체화된 자속구속형 전류제한기의 동작특성

  • Published : 2006.05.11

Abstract

Superconducting fault current(SFCLs) are expected to improve not only reliability but also stability of real power systems. The analysis on the single line-to-ground fault current of the integrated three phase flux-lock type SFCL, which consists of three flux-lock reactor wound on an iron core in each single phase and three YBCO thin films, was investigated in current limiting operating characteristics. We compared additive polarity winding with the subtractive one in the flux lock reactor. Its turns ratio each phase between the primary and the secondary coils is 63:42. When a single line-to-ground fault occurred in any phase, the peak value of line current in the fault phase of the additive polarity winding increased up to 31.44[A] during first-half cycle. On the other hand, the peak value in the subtractive polarity winding increased up to 81.77[A] under the same conditions. This is because the current flow between the primary and the secondary windings becomes to be additive or subtractive in each winding direction. We confirmed that the current limiting behavior in the additive polarity winding was more effective for a single-line-to ground fault.