Analysis of Partial Discharge Pattern in XLPE/EDPM Interface Defect using the Cluster

군집화에 의한 XLPE/EPDM 계면결함 부분방전 패턴 분석

  • Published : 2007.11.01

Abstract

This paper investigated the influence on partial discharge distribution of various defects at the model power cable joints interface using K-means clustering. As the result of analyzing discharge number distribution of ${\Phi}-n$ cluster, clusters shifted to $0^{\circ}\;and\;180^{\circ}$ with increasing applying voltage. It was confirmed that discharge quantity and euclidean distance between centroids were increased with applying voltage from the analyzing centroid distribution of ${\Phi}-q$ cluster. The degree of dispersion was increased with calculating standard deviation of ${\Phi}-q$ cluster centroid. The tendency both number of discharge and mean value of ${\Phi}-q$ cluster centroid were some different with defect types.

Keywords