The SAG Behavior of Overhead Conductor due to Forest Fire

산불에 의해 가열된 가공송전선의 이도거동

  • Published : 2007.11.01

Abstract

Because forest fire can give a serious damage to overhead conductors, the thorough understanding about sag behavior of burned conductor is very important in maintaining the transmission line safely. Therefore, a systematic investigation was carried out by heating method. As the heating temperature increases, drastic change of tensile strength of Al wire due to the softening of Al wire occurred. When Al wire is exposed to the flame(about $800^{\circ}C$) during only 13 seconds, the remained tensile strength of Al wire showed under 90%. and then sag of overhead conductor become deteriorated. The detailed results will be given in the text.