An Experimental Study on the Performance of Semi-Closed Loop Ground Heat Exchanger

반밀폐형 지중열교환기 성능에 관한 실험적 연구

  • 김욱중 (한국기계연구원 에너지기계연구센터) ;
  • 염한길 (한국기계연구원 에너지기계연구센터) ;
  • 이춘우 ((주)탑솔)
  • Published : 2007.11.06

Abstract

A semi-closed loop ground heat exchanger is proposed and its performance is compared through the measuring the effective thermal conductivity of the ground. In-situ tests based on the line source model are carried out to evaluate the thermal characteristics of each ground heat exchanger which has different penetration water flow rate. The test results show the increasing effective thermal conductivity of ground as the penetration water flow rate(PWFR) is increased. Therefore, the higher thermal performance of the proposed semi-closed ground heat exchanger can be expected.