Proceedings of the Korea Institute of Fire Science and Engineering Conference (한국화재소방학회:학술대회논문집)
- 2008.11a
- /
- Pages.444-449
- /
- 2008
Simulation of Pool Fire with Two Rooms Using CFAST Model
CFAST 모델을 이용한 이중격실화재 모사
- Ryu, Su-Hyun (Korea Institute of Nuclear Safety(KINS)) ;
- Keum, O-Hyun (Korea Institute of Nuclear Safety(KINS)) ;
- Kim, Wee-Kyung (Korea Institute of Nuclear Safety(KINS)) ;
- Kim, Yun-Il (Korea Institute of Nuclear Safety(KINS)) ;
- Bae, Young-Bum (Korea Institute of Nuclear Safety(KINS)) ;
- Park, Jong-Seuk (Korea Institute of Nuclear Safety(KINS))
- Published : 2008.11.13
Abstract
Fire model shall be verified and validated to reliably predict the consequences of fires within its limitations. This study aims to predict pool fire phenomena with two rooms using CFAST and to compare CFAST simulation results with PRISME experimental data which can be applicable to the fire of nuclear power plant facility. Five different mass loss rate(MLR) are used in the simulation and the simulated results of specific quantities such as temperature, chemical composition are compared to the experimental data. From this study, the CFAST simulation results with the proper MLR show better similarity and trend with pool fire experimental data.
Keywords