Frequency Dependence of Grounding Impedances of the Deeply-driven Ground Rods

심매설 접지전극의 접지임피던스의 주파수의존성

  • 김태기 (대한전기협회 기술기준처) ;
  • 강성만 (대한전기협회 기술기준처) ;
  • 이복희 (인하대학교 전기공학과)
  • Published : 2008.05.08

Abstract

Grounding impedance depends on the frequency of current flowing into a grounding system. Especially, the lightning gives a broad frequency spectrum from low frequency up to 1 MHz. So the grounding impedance related to high frequency current like lightning should be measured with high frequency source. In this paper, we described the grounding impedances of deeply-driven ground rods of 10 ${\sim}$ 48 m long with respect to the frequency of injected currents and the feed point. For the experiments, we used the wideband power amplifier which can produce sinusoidal voltages with the frequency ranges of DC ${\sim}$ 250 MHz. As a result, the longer the ground rod is, the lower the ground resistance is. However the grounding impedance of deeply-driven ground rod in the range of higher frequency is significantly increased. As a consequence, it is important to evaluate the high frequency performance of grounding systems for lightning protection.

Keywords