Transient impedance characteristics according to the injection position of deep-driven ground rods

심매설 접지전극의 전류인가위치에 따른 과도접지임피던스 특성

  • 이복희 (인하대학교 IT 공과대학 전기공학부) ;
  • 이봉 (인하대학교 IT 공과대학 전기공학부) ;
  • 이수봉 (인하대학교 IT 공과대학 전기공학부) ;
  • 이승주 (인하대학교 IT 공과대학 전기공학부) ;
  • 전병욱 (인하대학교 IT 공과대학 전기공학부) ;
  • 엄주홍 (기초전력연구원) ;
  • 조성철 (기초전력연구원) ;
  • 이태형 (기초전력연구원)
  • Published : 2008.05.08

Abstract

This paper presents the behaviors of transient and conventional grounding impedances of a deep-driven ground rods associated with the injection point of lightning impulse currents. The transient impedance of deep-driven ground rods under lightning impulse currents were higher than the static ground resistance. The transient grounding impedances strongly depend on the injection point and size of grounding electrodes and the rising time of impulse current. Reduction of ground system inductance is an important factor to lightning surge protection.