Korean Institute of Electrical and Electronic Materials

XLPE 전력케이블의 부분방전 측정을 위한 평면 루프 센서 설계에 관한 연구

  • Published : 2008.04.17

Abstract

In this study, The new type of loop antenna which detects the partial discharge was designed based on microstrip line technology. In diagnosis of power cable, partial discharge signal generally occurred at the frequency range lower than 100MHz because high frequency PD signals could be lost along the propagation path in the cable. The new type of loop antenna sensor has been studied by using Simulation software named CST microwave studio version 5.0. In partial discharge measuring experiments, commercial HFCT sensor was used as a reference sensor. Several experiments were made over HFCT sensor and loop antenna sensor in detection partial discharge on MV XLPE cable of 22.9kV. In this study, we have shown our loop antenna sensor can apply as a commercial HFCT sensor.

Keywords