An Experimental Study on the Performance of the Louver Fin Type Heat Exchanger by the Change of the Driving Condition

운전조건 변화에 따른 루버휜 열교환기 성능변화에 관한 실험적 연구

  • Kim, Jung-Kuk (Interdisciplinary Graduate School of Engineering Sciences, Kyushu University) ;
  • Koyama, Shigeru (Interdisciplinary Graduate School of Engineering Sciences, Kyushu University) ;
  • Kuwahara, Ken (Interdisciplinary Graduate School of Engineering Sciences, Kyushu University) ;
  • Kim, Dong-Hwi (Interdisciplinary Graduate School of Engineering Sciences, Kyushu University) ;
  • Park, Byung-Duck (Department of Automotive Engineering, Kyungpook National University)
  • 김정국 (큐슈대학교 총합이공학부) ;
  • 소산번 (큐슈대학교 총합이공학부) ;
  • 상원헌 (큐슈대학교 총합이공학부) ;
  • 김동휘 (큐슈대학교 총합이공학부) ;
  • 박병덕 (경북대학교 자동차공학과)
  • Published : 2008.06.25

Abstract

The present study was investigated the effect of the driving condition on the performance of a louver fin and tube type heat exchanger under frosting condition. Heat transfer rate and pressure drop by frost were experimentally investigated. Effects of the wet blub temperature and the shape of a fin on heat transfer performances has been also investigated. The key parameters were fin type(louver and corrugate fin) and the wet blub temperature of air (0.5, 1.0, $1.5^{\circ}C$). The heat transfer performance of the louver fin and tube type heat exchanger was higher by 0.89% than the corrugate fin type. As the wet blub temperature of air were increased, the heat transfer rate, pressure drop and mass of frost of three test models(Type A, B, C) were increased. Especially, the maximum heat transfer rate and maximum pressure drop were shown for the louver fin and tube type heat exchanger. As a experimental result, the enhancement factor(EF) of louver fin and tube type heat exchanger was $0.2{\sim}0.4$ due to the high pressure drop.

Keywords