IAQ improvement effect analysis in Dynamic Breathing Building(DBB)

숨쉬는 벽체를 적용한 건물에서의 실내공기질(IAQ) 개선 효과 분석

  • Park, Yong-Dai (Department of Architecture, Chungnam National University) ;
  • Lee, Jin-Sook (Department of Architecture, Chungnam National University) ;
  • Kang, Eun-Chul (Department of Renewable Energy, Korea Institute of Energy Research) ;
  • Lee, Euy-Joon (Department of Renewable Energy, Korea Institute of Energy Research)
  • Published : 2008.06.25

Abstract

In modern buildings, the air-tightness and insulation for energy saving resulted in degradation of Indoor Air Quality(IAQ). It has brought out new diseases such as New Building Syndrome(NBS) and Sick Building Syndrome(SBS) to the tenants of such buildings. As a result, researches on the Dynamic Breathing Building(DBB) are being undertaken to minimize energy loss as well as to improve IAQ. DBB is a state-of-the-art technology to build channels inside the wall so that air migrates between indoor and outdoor, which improves insulation performance and IAQ. This study attempts to evaluate the improvement of DBB employed in real buildings. As analyzing tools, IAQ improvement and particle degradation while were evaluated while the required indoor ventilation rate was satisfied. DBB were installed in the twin test cells at Korea Institute of Energy Research(KIER). From the test, IAQ was compared with outdoor air base on the concentration of particle matter(PM10). As a results, the concentration of particle dust (PM10) within the breathing walls was reduced by 80% at 0.7 ACH, 67% at 2 ACH, 63% at 3 ACH respectively. As ACH is higher, Dnamic Isulation(DI) and normal wall permit more PM10 particles being infiltrated.