Analysis of Comfortable Environment in the Classroom with Humidification and Ventilation in Winter

겨울철 가습 및 환기에 따른 교실내 쾌적환경 분석

  • Published : 2008.06.25

Abstract

This experimental study was to analyze thermal comfort and indoor air quality(IAQ) with ventilation and humidification in the classroom when system air conditioner was operated. The thermal comfort was estimated by the PMV index and the concentration of $CO_2$ and total suspended particle(TSP) were measured and compared with ventilation and humidification. As a result, the class room temperature distribution was $2{\sim}5^{\circ}C$ low during operating ventilation system and humidification. At 60% RH, PMV values of measuring points were ranged from +0.5 to -0.5 indicating optimal the range of thermal comfort. The average concentration of $CO_2$ gas and TSP were reduced 645 ppm, 0.17 mg/$m^3$ respectively, during operating the ventilation system. From the results, to maintain comfortable environment in the heated classroom, the ventilation and humidification were needed in winter season.