A Study on Performance of Air-condition Linked by Quick Disconnect Coupling

급속분리커플링으로 연결된 에어컨의 운전성능에 관한 실험적 연구

  • 조수 (한국에너지기술연구원 건물열성능센터) ;
  • 이수열 (한양대학교 대학원 기계공학과) ;
  • 성욱주 (한국에너지기술연구원 건물열성능센터) ;
  • 박희문 ((주)삼영) ;
  • 심경종 ((주)삼영) ;
  • 김우승 (한양대학교 대학원 기계공학과)
  • Published : 2008.11.21

Abstract

This study analyzed operation characteristics of air-condition piping is made by quick disconnect coupling. Air-conditioning consists of central compressor 3HP capacity and R22 refrigerant. We experimented with two operation cycles of air-condition under the same environment; one is with quick disconnect coupling. The other is without quick disconnect coupling. As a result, we can observe whether the condensation temperature of former increased by about 3-5. Furthermore, COP decreased by about 10%.

Keywords