Performance Analysis of Indoor GHP for R410A Application

R410A 냉매를 이용한 GHP용 고효율 실내기 성능특성

  • Published : 2009.06.25

Abstract

The objectives of this paper are to study the effects of thermal and geometric conditions on the performance of indoor heat exchanger with R410A. This study carried out experimental and numerical analysis for indoor heat exchangers. In the experimental study, capacity of the indoor unit was estimated 8.3 kWh with the valve opening rate of 95% for the 50% partial operation condition. The air temperatures were measured using 80 thermocouples. This study also compared experimental data with the calculated data for the outlet temperature and the tube length. It is found that the relative errors between the experiment data and the calculated result are 4.2% and 0.5% for the outlet temperature and the tube length, respectively.