열펌프의 난방운전시 핫가스 바이패스에 따른 성능 특성에 관한 실험적 연구

An Experimental Study on the Performance Characteristics of a Heat Pump System in the Heating Operation Mode with the Hot Gas Bypass

  • 안재환 (고려대학교 기계공학부 대학원) ;
  • 주영주 (고려대학교 기계공학부 대학원) ;
  • 조일용 (고려대학교 기계공학부 대학원) ;
  • 강훈 (고려대학교 기계공학부) ;
  • 김용찬 (고려대학교 기계공학부) ;
  • 최종민 (국립한밭대학교 기계공학부)
  • 발행 : 2009.06.25

초록

When the suction pressure of compressor decreases under its limit, the compression ratio is increased causing the malfunctions of compressor. As the method to decrease the compression ratio, hot gas bypass system is usually adopted in heat pump system. In the hot gas bypass system, the discharged gas from the compressor is bypassed into the compressor suction, which causes the increase of suction pressure and the decrease of compression ratio. In this study, the characteristics and performances of the hot gas bypass system in heat pump was investigated experimentally with a variation of the bypass flow rate ratio. With the increase of the bypass rate ratio, the compressor suction pressure was increased, even though the total capacity and COP was decreased. From the analysis of the experimental results, the optimum pressure control algorithm was suggested in this study.