Ice slurry transporting and branching characteristics for the district cooling

지역냉방을 위한 아이스슬러리 시스템의 수송 및 분기 특성

  • Lee, Sang-Hoon (Korea Institute of Science and Technology) ;
  • Yoo, Ho-Seon (Department of Mechanical Engineering, Soongsil University) ;
  • Lee, Yoon-Pyo (Korea Institute of Science and Technology) ;
  • Lee, Chang-Jun (District Heating Technology Research Institute, Korea District Heating Corp) ;
  • Kwon, Hyeok-Min (District Heating Technology Research Institute, Korea District Heating Corp)
  • 이상훈 (한국과학기술연구원) ;
  • 유호선 (숭실대학교 기계공학과) ;
  • 이윤표 (한국과학기술연구원) ;
  • 이창준 (한국지역난방공사 지역난방기술연구소) ;
  • 권혁민 (한국지역난방공사 지역난방기술연구소)
  • Published : 2009.06.25

Abstract

The research are performed to check the characteristics of the ice slurry transport system for the district cooling. The system are installed at the 1st floored building which is as large as the $1204\;m^2$ ($86\;m{\times}14\;m$), and the pumping power and branching characteristics are measured by transporting of the ice slurry. The ice slurry transporting pipe is as long as 200 m. For the same cooling load, the higher IPF is, the lower the transporting flow rate and the pumping power are. But when the IPF is higher than 15%, no less decrease of the pumping power does happen. For the branching characteristics, through the branch pipe where the flow resistance is higher, the higher IPF is measured. A little higher IPF is measured at the thermal expansion branch.