시스템분배기 소음방지 및 성능개선방안 연구

A Study on the Noise Reduction and Performance Improvement of the Hot Water Distributing System

  • 김용기 (한국건설기술연구원 설비플랜트연구실) ;
  • 이태원 (한국건설기술연구원 설비플랜트연구실) ;
  • 한태수 (한국건설기술연구원 설비플랜트연구실) ;
  • 유선학 (신한콘트롤밸브(주) 기술부)
  • Kim, Yong-Ki (Plant Research Division, Korea Institute of Construction Technology) ;
  • Lee, Tae-Won (Plant Research Division, Korea Institute of Construction Technology) ;
  • Han, Tae-Su (Plant Research Division, Korea Institute of Construction Technology) ;
  • Yoo, Sun-Hak (Engineering Dept., Shin Han Control Valve Co., Ltd.)
  • 발행 : 2009.06.25

초록

Noise is one of the major environmental problems in human life. But hot water distributers with the flow rate control valve bring about often noise according to the heating control condition in residential buildings. The sound power level increased as the flow rate and pressure difference increased. And thus, experimental analyses for the flow rate control and the pressure difference control were carried out in this study to reduce the noise emitted from the flow rate control valve. As the results, the flow rate control method using a SMA(Shape Memory Alloy)-valve and the flow rate control system using a pressure difference sensor can be expected to control noise in the region of below 50 dB of sound power level.