A study on performance of outdoor air flow rate through viovent for hybrid ventilation equipment

자연급기구내 플리머필터 설치 시 외기 침기량 분석에 관한 연구

  • Published : 2009.06.25

Abstract

This test was progressed in the test house of KICT as sectional research of Center for Sustainable Housing. It included a ventilation rate of hybrid ventilation equipment, temperature, and gas test using the SF-6. The purpose of this test is to demonstrate the performance of viovent by estimating an outdoor air flow rate through viovent which the flimmer filter is installed and decide the leakage after operating the constant airflow fan within a house. First, the outdoor airflow rate through viovent measured $130\;m^3/h$ more than a legal required ventilation rate, $104\;m^3/h$. And then it sufficiently satisfy a legal standard, 0.7 air change/h. Secondly, the result of this test exposes that the leakage in the residence is about $20{\sim}25%$. Especially, the outdoor air flowing through the gate occupies 50% of the total leakage.