지열히트펌프를 이용한 습식.건식 바닥난방 성능평가 연구

A Study on Comparison of Capacity between Wet.Dry Floor Heating Systems Using Geothermal Heat Pump

  • 발행 : 2009.11.25

초록

The present study conducted comparative evaluation of wet dry floor heating systems using geothermal heat pump. Circulation hot water from geothermal heat pump which is $10{\sim}15^{\circ}C$ lower than that from boiler was used. In order to access indoor temperature ($25^{\circ}C$) it took 74 minutes for dry type and 247 minutes for wet type. Average floor temperature was $23.89^{\circ}C$ for wet type and $32.66^{\circ}C$ for dry type. Energy saving rate gradually increased by 66% after 138 minutes. In the results, for floor heating system using low temperature circulation water, wet type was not enough to meet stable and comfortable radiant floor heating due to low floor temperature and access time to indoor set temperature. While dry type was practicable for stable floor heating due to fast rise of indoor set temperature and comfortable floor temperature.