Transient impedance characteristics of counterpoise according to the soil structures

대지구조에 따른 매설지선의 과도접지임피던스 특성

  • 이복희 (인하대학교 IT 공과대학 전기공학부) ;
  • 이봉 (인하대학교 IT 공과대학 전기공학부) ;
  • 정동철 (인하대학교 IT 공과대학 전기공학부) ;
  • 김기복 (인하대학교 IT 공과대학 전기공학부) ;
  • 조성철 (기초전력연구원)
  • Published : 2009.10.09

Abstract

This paper presents the characteristics of grounding impedance of counterpoises buried at various soil structures. Grounding impedance measurements were made by the Fall-of-Potential method. The experiments were carried out in 50 m counterpoise of 25 $mm^2$ buried at a depth of 0.5 m. The test current was injected by the impulse generator having the front time of $1{\sim}60{\mu}s$. As a result, the soil structures greatly influences on the grounding impedance characteristics of counterpoise. The transient grounding impedances strongly depend on the injection mint and the front time of impulse current.

Keywords