Risk Assessment of High Pressure HCNG Refueling Station Explosion by Numerical Simulation

시내버스용 HCNG 고압가스 충전소의 폭발 위험성 해석

  • 강승규 (한국가스안전공사 가스안전연구원) ;
  • 김영구 (한국가스안전공사 가스안전연구원) ;
  • 최슬기 (한국가스안전공사 가스안전연구원) ;
  • 권정락 (한국가스안전공사 가스안전연구원)
  • Published : 2014.11.27

Abstract

This study has been conducted for evaluation of qualitative/quantitative risk of HCNG filling station. In case of fire explosion occurred because of hydrogen, CNG, and HCNG leaking on same conditions, maximum overpressure was measured as 30kPa for hydrogen, 3.5kPa for HCNG, and 0.4kPa for CNG. The overpressure of HCNG was measured 7.75 times higher than that of CNG, but it was only 11.7% compared with hydrogen. When the explosion was occurred, in case of hydrogen, the measured influential distance of overpressure was 59m and radiant heat was 75m. In case of CNG, influential distance of overpressure was 89m and radiant heat was 144m would be estimated. In case of 30% HCNG that was blended with hydrogen and CNG, influential distance of overpressure was 81m and radiant heat was 130m were measured. As the explosion occurred with the same sized container that had 350bar for hydrogen and 250bar of CNG and HCNG, the damage distance that explosive overpressure and radiant heat influenced CNG was seen as the highest. HCNG that was placed between CNG and hydrogen tended to be seen as more similar with CNG.

Keywords