Effects of tube-support parameters on damping of heat exchanger tubes in liquids

튜브지지대 인자가 열교환기 튜브의 감쇠에 미치는 영향

  • 김범식 (한국에너지연구소 발전로기계설계실)
  • Published : 1988.09.01

Abstract

Damping information is required to analyse heat exchangers for flow-induced vibration. The most important energy dissipation mechanisms in heat exchanger tubes are related to the dynamic interaction between tube and support. In liquids, squeeze-film damping is dominat. Simple experiments were carried out of a two-span tube with one intermediate support to investigate the effects of tube-support parameters, such as: tube-support thickness, diametral clearance, tube eccentricity, tube span length, location of tube-support, and nature of dynamic interaction between tube and tube-support. The results show that squeeze-film damping is much larger for lateral-type motion than for rocking-type motion at the support. Eccentricity was found to be very important. Diametral clearance, support thickness and frequency are also very relevant. The effects of these parameters on squeeze-film damping are formulated and proposed in a semi-empirical expression.

본 연구에서는 상하운동 또는 좌우흔들림운동하에서의 튜브진동에 대한 실험 을 통하여 튜브지지대 인자의 영향을 고찰하고자 하였다.실험은 양단이 고정된 튜 브의 중앙에 지지대가 있는 두마디 튜브의 실험장치에서 수행되었다. 실험시 고찰된 인자들은 튜브편심율, 튜브지지대 두께, 튜브와 튜브지지대간의 간격, 튜브지지대의 위치, 튜브주파수, 선형도, 그리고 튜브거동 형태(nature of the dynamic interaction )등이다.