간이 에너지 계산법과 동적 열부하 계산법의 비교 연구

A Comparison of the ASHRAE Simplified Energy Analysis Procedure with the HASP/ACLD Results

  • 김두천 (육군사관학교 기계공학과) ;
  • 최진희 (육군사관학교 기계공학과) ;
  • 원영수 (육군사관학교 기계공학과)
  • 발행 : 1989.08.01

초록

The ASHRAE Simplified Energy Analysis Procedure using the Modified Bin Method(SEAP) is compared with the hourly calculation program, HASP/ACLD. The HASP/ACLD model office building with VAV system in Seoul is used as the basis for comparison. And the parameters considered are glass to wall area ratio and internal heat gains. The results show that SEAP predictions of annual energy use agree with HASP/ACLD predictions within 5% deviation. But there is a large difference in cooling and heating energy as glass to wall area ratio is varied. The SEAP cooling energy is 65-85% and the heating energy is 104-160% of the HASP/ACLD results. This is probably due to the solar heat gain data. the data related to the SEAP must be developed prior to use it.

키워드

과제정보

연구 과제 주관 기관 : 한국과학재단