Themodynamic Characteristics of a Two-Stage Binary Absorption Cycle

2단(段) 2원(元) 흡수(吸收)사이클의 특성(特性)에 관(關)한 연구(硏究)

  • 이용화 (유한전문대학 건축설비과) ;
  • 이동호 (인천대학교 산업안전공학과) ;
  • 백목효부 (동경농공대학 기계시스템공학과) ;
  • 서정윤 (인하대학교 기계공학과)
  • Published : 1995.05.31

Abstract

This paper concerns the study of a two-stage binary absorption cycle employing the refrigerant/absorbent combinations of $LiBr/H_2O$ and $NH_3/H_2O$. This cycle consists of coupling two single-effect absorption cycles so that the first stage absorber and condenser produces heating water to evaporate refrigerant in the evaporator of the second stage. The effect of operating variables such as evaporator temperature, condenser and absorber temperature, and generator temperature on the coefficient of performance and temperature lift have been studied for two-stage binary absorption heat pump systems. It is found that this cycle has a large temperature lift at $105^{\circ}C$ of optimum generator temperature to obtain $50^{\circ}C$ of condenser temperature.

본 연구는 $H_2O/LiBr$$NH_3/H_2O$계를 사용하는 2단2원 흡수식 사이클의 특성에 관한 연구이다. 이 사이클은 2개의 단효용 사이클로 이루어져 있으며, 저온단의 흡수기와 응축기에서 얻어진 열을 고온단의 증발기에서 이용하는 사이클로서 저온단의 증발기 및 응축기의 온도, 재생기 온도, 열교환 온도차를 파라메터로 하여 계산한 결과 다음과 같은 결론을 얻었다. 2단2원사이클의 성립범위를 확인하였으며 본 계산조건에서 $50{\sim}70^{\circ}C$의 승온폭을 얻을 수 있었다. 또한 $50^{\circ}C$의 난방온도를 얻기위한 최적재생온도는 $105^{\circ}C$, 최대 COP를 얻기위한 저온측사이클의 응축압력은 $16^{\circ}C$, 그리고 이 조건에서 저온측 사이클의 응축압력을 단효용 사이클의 경우보다 낮게 억제하는 것이 가능함을 알았다.