An Experimental Study on the Performance of Fin-Tube Heat Exchanger under Frosting Condition

착상조건하에서 핀-관 열교환기 성능에 관한 실험적 연구

  • Published : 1995.05.01

Abstract

In this study, the experiment with 2rows-2columns fin-tube heat exchanger under forced convection and frosting condition is performed. The influence of each operating condition(the temperature of air, the humidity of air, the velocity of air, the temperature of coolant) on the growth of frost layer, air-side pressure drop, and characteristics of heat transfer is investigated. The experimental results show that the frost thickness increases rapidly in the early stage of frost formation and increases linearly after sometime. The frost thickness increases with the increase of the inlet air humidity and velocity and the decrease of inlet air temperature and coolant temperature. It is also found that the total energy transfer rate increases with the increase of inlet air temperature and velocity and with the decrease of inlet air humidity and coolant temperature.

Keywords