인버터 열펌프의 주파수 및 모세관 길이 변화에 따른 시스템 성능특성의 실험적 연구

An experimental study on the performance of inverter heat pump with a variation of frequency and capillary size

  • 최종민 (고려대학교 기계공학과 대학원) ;
  • 김용찬 (고려대학교 기계공학과) ;
  • 김종엽 (삼성전자 생활시스템연구소) ;
  • 배영돈 (삼성전자 생활시스템연구소)
  • 발행 : 1997.02.01

초록

An experiment study was performed to investigate the optimum cycle of an inverter heat pump as a function of frequency. The performance of the inverter heat pump with the rated cooling capacity of 4141W(3550kcal/h) was measured with a variation of frequency, indoor and outdoor temperature, and length of capillary tube in the psychrometric test room. As a base case, the inverter heat pump with the standard capillary length of 1000mm which was optimum size for the frequency of 60Hz and ARHRAE Test condition A was tested by varying frequency from 30Hz to 80Hz. Then, the optimum cycle was invesigated by varying the length of capillary tube at each frequency levels of 30, 60 and 80Hz. Based on the experimental data, the change of system characteristics between the optimum and the base case were analyzed for each selected frequency levels. Generally, for low frequency level(30Hz), the longer length of the capillary tube compared with the standard size showed the higher EER, while for high frequency level(80Hz) the shorter length of the capillary tube showed the higher EER.