포화를 방지하기 위한 보호용 철심 변류기 설계 방법

A Design Method of Iron-cored CTs To Prevent Satruation

  • 발행 : 1999.02.01

초록

Current transformer (CT) saturation may cause a variety of protective relays to malfunction. The conventional CT is designed that it can carry up to 20 times the rated current without exceeding 10% ratio error. However, the possibility of CT saturation still remains if the fault current contains substantial amounts of ac and/or dc components. This paper presents a design method of iron-cored CTs for use with protective relays to prevent CT saturation. The proposed design method determines the core cross section of the CT; it employs the transient dimensioning factor to consider relay's operating time (duty cycle) and dc component as well as ac components contained in the fault current, and symmetrical short-circuit current factor to consider as well as ac components contained in the fault current, and symmetrical short-circuit current factor to consider the biggest fault current. The method designs the cross section of CTs in cases of reclosure and no reclosure.