A study on the behavior of frost formation according to surface characteristics in the fin-tube heat exchanger

핀-관 열교환기의 표면특성에 따른 착상 거동에 관한 연구

  • Published : 1999.05.01

Abstract

In this study, the behavior of frost formation according to surface characteristics in the fin-tube heat exchanger has been examined experimentally. The results show that the thickness of the frost which is attached to the hydrophilic heat exchanger becomes thin and the air pressure drop is smaller than that of bare aluminium heat exchanger However, the frost mass of hydrophilic heat exchanger is more than the bare one. Hence, high density frost is attached to hydrophilic heat exchanger. The sensible and latent heat flux of hydrophilic heat exchanger is bigger than that of bare one, but the increasing amount is very small and the improvement of thermal performance is also very small. The variation of fin-pitch of heat exchanger shows little influence on frost formation and hydrophilic heat exchanger loses its surface characteristics rapidly with increasing relative humidity.

Keywords