Comparative analysis of the minimum capacity of an ice-on-coil thermal storage system for various operation strategies

관외 빙착형 빙축열시스템의 운전방식에 따른 최소용량 비교

  • Published : 1999.05.01

Abstract

An ice storage cooling facility with cooling capacity of 150㎾ has been constructed for the purpose of developing optimal design and control strategy for an ice storage system. As the first step to this purpose, a computer program has been developed to simulate the operation of the ice storage system and examined precisely by comparing the results with those measured from the test facility. With the simulation program verified from the comparison, a design procedure has been developed to determine the minimum capacity required for each operation strategy available commercially. It is shown that the minimum sizes of the chiller and the storage tank are strongly dependent on the control strategy, i.e., chiller priority or storage priority, but less affected by the arrangement method, i.e., chiller upstream or chiller downstream.

Keywords