Acoustic Emission Testing in Cylindrical-Type Storage Tank

원통형 저장탱크의 음향방출시험

  • 권정락 (한국가스안전공사 가스안전기술연구센터) ;
  • 류근준 (한국가스안전공사 가스안전기술연구센터) ;
  • 이태희 (한국가스안전공사 가스안전기술연구센터) ;
  • 김지윤 (한국가스안전공사 가스안전기술연구센터)
  • Published : 2000.03.01

Abstract

In order to investigate the structural defects of a cylindrical-type toluene storage tank, we carried out the acoustic emissions. The storage tank was manufactured with high strength steel in 1978 and its's first and second courses from bottom were entirely repaired, recently. Acoustic emissions were monitored with real time according to load sequences in the $75{\~}84\%$ level range of maximum allowable load. Our results show a non-genuine acoustic emissions as well as a genuine characteristics. The pseudo emissions considered as valve noises were transiently occurred on shut-off processes of inlet valve regardless of water loading. The acoustic emission events occurred during water filling phase were estimated due to defects, and in the $75{\~}84\%$ test load level no evidences of defect growth were observed. Those defects were ascertained as weld cracks and porosities through the post radiography testing conducted near active sensors.

원통형 톨루엔 저장탱크의 구조결함을 조사하기 위하여 음향방출시험을 수행하였다. 원통형 저장탱크는 고장력강으로 제작되었으며, 최근에 저장탱크의 하부 1 및 2단은 전면 보수되었다. 음향방출은 최대설계하중의 $75{\~}84\%$ 레벨영역에서 하중절차에 따라 실시간으로 모니터링 되었다. 시험결과는 순수 음향방출뿐만 아니라 유사 음향방출특성도 보여준다. 밸브잡음으로 판단되는 유사 방출들은 하중과는 무관하게 밸브잠금과정에서 과도적으로 발생되었다. 충수과정에서 발생된 순수 음향방출들은 결함에 기인하며, $75{\~}84\%$의 시험하중영역에서는 성장을 하지 않는 것으로 평가되었다. 이 결함들은 활성센서들을 중심으로 수행된 방사선시험을 통하여 용접균열과 기공인 것으로 밝혀졌다.

Keywords