Nucleate Pool Boiling of a Structured Enhanced Tube Used in a Flooded Refrigerant Evaporator

  • Kim, Nae-Hyun (Department of Mechanical Engineering, University of Inchon) ;
  • Cho, Jin-Pyo (Department of Mechanical Engineering, University of Inchon) ;
  • Choi, Kuk-Kwang (Department of Mechanical Engineering, University of Inchon)
  • Published : 2000.11.01

Abstract

In this study, pool boiling performance of a structured enhanced tube for a flooded refrigerant evaporator was experimentally investigated. Tests were performed for three different refrigerants(R-11, R-123, R-l34a). Compared with the heat transfer coefficients of the smooth tube, the heat transfer coefficients of the enhanced tube were 6.6 times larger for R-11, 6.0 times larger for R-123 and 3.5 times larger for R-l34a, which are comparable with the performance of foreign products. The heat transfer coefficients of R-l34a was higher than those of R-11 or R-123, both for the enhanced tube and for the smooth tube. At 4.4$^\circ$C saturation temperature, however, the heat transfer coefficients of R-l34a was approximately the same as those of R-11. The effect of the saturation pressure on the boiling performance was similar to that of the smooth tube-the heat transfer coefficient increased as the saturation pressure increased.