Abstract
Cold-formed steel truss system was reviewed in order to improve the various problems associated with the steel floor joist system, such as the structural deficiency caused by web punching and others. Two types of floor truss system using cold-formed steel were reviewed during this research project, including the square end type(SE type) and underslung type(EE type). The strctural behavior was analyzed using the AISI design criteria and various bending tests. Test results show that the SE type floor truss proved to be more efficient than the EE type when it is subjected to concentrated load, and that the unbraced length of the floor truss about the weak axis has much importance on the buckling strength of the floor truss. Test results indicate that their values surpass the calculated values predicated through the AISI design criteria.
기존 바닥조이스트의 문제점을 해결하기 위해 냉간성형강 평트러스 시스템에 대한 연구를 진행하였다. 냉간성형강 평트러스 시스템은 기존 스틸 조이스트 시스템과 유사한 구조형식을 취하고 있으며, 무게 대비 성능이 우수하고, 설비라인을 바닥 구조재와 동일 선상에 배치할 수 있다는 장점을 가지고 있다. 본 연구에서는 Square End Type(SE Type), Underslung Type(EE Type) 평트러스의 구조적 거동에 대한 분석과 더불어, AISI 설계기준을 토대로 평트러스의 설계하중에 대한 평가가 진행되었다. 그리고 휨 실험을 통해 평트러스의 좌굴 거동에 대한 조사를 진행하였다. 실험결과 SE Type 평트러스가 EE Type 평트러스 보다 집중하중에 유리한 것으로 확인되었으며, 약축방향에 대한 비보강길이가 평트러스의 성능에 중요한 영향을 미치는 것으로 분석되었다. 그리고 실험을 통해 측정된 평트러스의 좌굴하중은 AISI 설계기준 값을 충족시키는 것으로 확인되었다.