지중송전케이블계통에서 절연통의 과전압 해석 및 억제대책 검토

Analysis of Overvoltage and Reduction Methods of Insulation Joint Box in Underground Power Cable Systems

  • 발행 : 2002.02.01

초록

This paper describes the overvoltage analysis and reduction methods of insulation joint boxes in underground transmission power cables when direct lightning surge strikes to overhead transmission line. An actual 154kV combined transmission line with underground Power cables was modelled in ATPDraw for simulation. Simulations were performed to analyze the overvoltage between insulation joint boxes, sheath-to-ground voltage according to the distance between cable conductors, cable lengths, burying types, CCPU connection types. The most effective method to reduce the induced overvoltage of Insulation joint boxes was proposed. It is evaluated that the proposed reduction method riven from the detailed simulations can be effectively applied to the actual underground power cable systems.

키워드

참고문헌

  1. 한국전력공사, '지중송전실무 I', 1996
  2. 한국전력연구원, '지중송전계통의 접지기술 정립에 관한 연구', 1998
  3. 김석수, 조한구, 박태곤, '지중송전케이블의 절연통 보호 대책 및 방식층보호장치의 특성', 한국전기전자재료학회, pp. 72-75, 2001
  4. N. Nagaoka, A. Ametani, 'Transient Calculations on Crossbonded Cables', IEEE. Trans. PAS., No. 5, pp. 779-787, April 1983 https://doi.org/10.1109/TPAS.1983.317940
  5. B. Gustavsen, J. Sletbak, 'Transient Sheath Overvoltage in Armoured Power Cable', IEEE Trans. Power Delivery, Vol. 11, No. 3, pp. 1594-1600, 1996 https://doi.org/10.1109/61.517521
  6. 이준성, 이종범, 김영, '방식층보호장치의 설치에 따른 지중송전케이블 시스유기전압 해석', 대한전기학회지, Vol. 49, No. 1, 2000
  7. 기상청, '낙뢰연보', 1999
  8. M.A. Uman, 'Lightning', Dover Pub. Inc., N.Y, 1969
  9. 전력연구원, '전력계통 과도해석 프로그램의 이론 및 활용, I, II, III
  10. ATP Rule Book, ATP Salford version of EMTP, Vol. I, II