온돌을 이용한 바닥복사냉방의 제습시스템 적용에 관한 연구

A Study on the Application of the Dehumidification System for Radiant Floor Cooling Using Ondol

  • 발행 : 2002.07.01

초록

This study has been conducted to evaluate the applicability of the control method in the dehumidification-integrated radiant floor cooling system in terms of stability of the room air temperature and the control variables through experiments. To do this, the relationship between the control variables in preventing floor surface condensation is first analyzed and the control method is predetermined through simulations. The results are as follows. First, it is necessary to determine the operation status of the dehumidification system according to the relationship between floor surface temperature and dew point temperature in the conditioned space. Second, outdoor reset with indoor temperature feedback control is better than on/off bang-bang control with respect to temperature stability in controlling the room air temperature and the possibility of energy savings. Finally, the humidity sensor can be located with the current thermostat in that there are small differences in absolute humidity in vertical distribution.

키워드

참고문헌

  1. Koo, S. Y., Kim, Y. Y., Seok, H. T., Lee, H. W. and Kim, K W., 2000, A Study on the applicability of radiant cooling using Ondol, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 12, No. 2, pp. 200-208
  2. Kim, Y. Y. and Kim, K. W., 2001, A study on the thermal environmental analysis and the application of radiant floor cooling in apartment building, Korean Journal of Airconditioning and Refrigeration Engineering, Vol. 13, No. 6, pp. 541-548
  3. Kim, Y. Y., Yoon, H. L. and Yeo, M. S., 2001, A study on the control of water flow and temperature in the radiant cooling system through simulations, Korean Journal of AirConditioning and Refrigeration Engineering, Vol. 13, No. 6, pp. 532-540
  4. Kim, Y. Y., Lim, J. H., Yeo, M. S. and Kim, K. W., 2001, An experimental study on control performance of radiant floor cooling using Ondol, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 13, No. 11, pp. 1165-1173
  5. Lee, S. Y., Hwang, S. H., Kim, K. H. and Leigh, S. B., 2002, An experimental study for evaluating performance of radiant floor cooling system integrated with dehumidification, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 14, No. 2, pp. 142-152
  6. Imanari, T., Omori, T. and Bogaki, K., 1999, Thermal comfort and energy consumption of the radiant ceiling panel system, Comparison with the conventional all-air system, Energy and Buildings, Vol. 30, pp. 167-175
  7. Yeom, J. K., 2000, Survey on electricity consumption characteristics of home appliances, Korea Electric Power Co., RP-31003
  8. Kitagawa, K., Komoda, N., Hayano, H. and Tanabe, S., 1999, Effect of humidity and small air movement on thermal comfort under radiant ceiling by subjective experiments, Energy and Buildings, Vol. 30, pp. 185-193 https://doi.org/10.1016/S0378-7788(98)00086-3
  9. McQuiston, F. C., 1992, Cooling and heating load calculation manual(2nd edition), ASHRAE 2001, pp. 28.4-28.5
  10. Matsuki, N., Nakano, Y, Miyanaga, T, Yokoo, N. and Oka, T, 1999, Performance of radiant cooling system integrated with ice storage, Energy and Buildings, Vol. 30, pp. 177-183 https://doi.org/10.1016/S0378-7788(98)00085-1
  11. Olesen, B. W., 1977, Thermal comfort requirements for floors occupied by people with bare feet, ASHRAE Transactions 83(2)
  12. Olesen, B. W., 2002, Introduction to thermal comfort standards and to the proposed new version of EN ISO 7730, Energy and Buildings, Vol. 34, pp. 537-548 https://doi.org/10.1016/S0378-7788(02)00004-X
  13. Michael, J. B., HVAC 2 tool kit - A toolkit for secondary HVAC System Energy Calculations, ASHRAE, 1993, pp. 81-96
  14. McQuiston, F. C; 1992, Cooling and heating load calculation manual, 2nd ed., ASHRAE, p.5.7