R410A 냉매를 사용한 열펌프용 열교환기의 형상에 따른 성능특성 연구

A Study on Performance Characteristics of Heat Exchanger for Heat Pump with R410A Refrigerant

  • 정규하 (삼성전자 시스템가전사업부 가전연구소 냉공조그룹) ;
  • 박윤철 (제주대학교 기계에너지생산공학부) ;
  • 오상경 (삼성전자 시스템가전사업부 가전연구소 냉공조그룹)
  • 발행 : 2004.04.01

초록

The air and refrigerant side heat transfer performances are key parameters to improve heat transfer efficiency of the heat exchanger including the fan performance. Design of the fins, treatment of the tube inside, tube diameter and tube array effect heat transfer performance of the heat exchanger. The heat exchanger is used as a condenser at cooling mode and used as an evaporator at heating mode in the heat pump system. The heat pump system uses R410A as the refrigerant. The heat exchangers are consisted with 7 mm diameter tubes with slit-type fins. The study was conducted with variation of arrangement of the refrigerant path and air flow rate and refrigerant pressure drop and heat transfer rate were measured with a code tester. The capacity of the 3 path heat exchanger is more efficient than 2 or 4 path heat exchangers in heating or cooling modes.

키워드

참고문헌

  1. The Int. Symp. on HCFC Alternative Refrigerants Performance and reliability of room air conditioner using R410A Nonaka,M.(et al.)
  2. Ref. v.72 no.835 Room A/C Nakayama,M.(et al.)
  3. Sanyo Technical Review v.30 no.1 RAC with alternative refirgerant R410A Akutsu,M.(et al.)
  4. Korea Journal of Air-Conditioning and Refrigeration Engineering v.15 no.2 The study of Performance evaluation coefficient of fin and tube heat exchangers with frosting Choi,B.J.;Hwang,J.H.;Shin,J.M.
  5. Proceeding of International CFC and Halon Aternative Conference Comparison of R407C and R410A with R22 in a 10.5 kW residential central air-conditioner Murphy,F.T.;Low,R.E.;Gilbert,B.E.;Linton,J.W.;Snelson,W.K.;Hearty,P.F.
  6. Korea Journal of Air-Conditioning and Refrigeration Engineering v.15 no.3 Comparison of performance veriation between R-22 and R410A refrigeration systems Park,T.J.;Lee,M.K.;Jeong,J.H.;Chang,K.S.
  7. Korea Journal of Air-Conditioning and Refrigeration Engineering v.14 no.9 An experimental study on condensation characteristics of slit fin-tube heat exchanger using alternative refrigerants Jeon,C.D.;Jang,K.K.;Kang,S.H.;Lee,J.