Combustion Characteristics of Fiber Reinforced Plastic by Cone Calorimeter

콘칼로리미터를 이용한 섬유강화플라스틱(FRP)의 연소특성

  • 이근원 (한국산업안전공단 산업안전보건연구원) ;
  • 김관응 (한국산업안전공단 산업안전보건연구) ;
  • 이두형 (한국화재보험협회 부설 방재시험연구워)
  • Published : 2004.06.01

Abstract

This study describes to assess combustion characteristics of fiber reinforced plastic (FRP) that is used an elements of building or structure in workplace. The combustion characteristics of the fiber reinforced plastic were carried out using by a Cone Calorimeter according to ISO 5660 standard. As the results of this study, the time to ignition and heat release rate of the fiber reinforced plastic was differ with heat flux of irradiance and content of flame retardant agent. The heat release rate of the fiber reinforced plastic was increased with increasing heat flux of irradiance. The flashover propensity of the fiber reinforced plastic using time to ignition and peak heat release rate was examined according to classification method by R.V. Petrella.

본 연구는 작업장의 건축물이나 구조물의 구성요소로 사용되어지는 섬유강화플라스틱의 연소특성을 평가하였다. 섬유강화플라스틱의 연소특성은 ISO 5660에 따라 콘칼로리미터를 사용하여 수행하였다. 섬유 강화플라스틱의 착화시간과 열방출율은 복사열과 난연제의 함량에 따라 달랐다. 섬유강화플라스틱의 열방출율은 복사열의 증가에 따라 증가하였다. 섬유강화플라스틱의 착화시간과 최대 열방출율을 이용하여 플래쉬오버(Flashover)의 가능성을 Petrella가 제시한 분류방법에 따라 검토하였다.

Keywords

References

  1. G. Gallina, E. Bravin, C. Badalucco, G. Audisio, M. Armanini, and A. De Chirico, 'Application of Cone Calorimeter for the Assessment of Class of Flame Retardant for Polypropylene', Fire and Materials, Vol. 22, pp.15-18(1998) https://doi.org/10.1002/(SICI)1099-1018(199801/02)22:1<15::AID-FAM626>3.0.CO;2-3
  2. U. Sorathia, G. Long, T. Gracik, M. Blum, and J. Ness, 'Screening Tests for Fire Safety of Composites for Marine Applications', Fire and Materials, Vol. 25, pp.215-222(2001) https://doi.org/10.1002/fam.771
  3. 이근원, 김관응, '발포 플라스틱의 착화특성 및 연소가스 분석', 산업안전학회지, Vol. 16, No. 1, pp.48-52(2001)
  4. Babrauskas and S. J. Grayson, Heat Release in Fires, Elselvier Science Publishing Co., New York (1992)
  5. 이근원, 김관응, '콘칼로리미터를 이용한 플라스틱 단열재의 화재특성', 한국화재.소방학회 논문지, Vol.17 No.1, pp 76-83(2003)
  6. 이근원, '산업용 단열재의 화재위험 특성에 관한 연구'. 연구원 2000-18-138, 한국산업안전공단 산업안전보건 연구원(1999)
  7. ISO 5660-1, Reaction to Fire, Part 1. Rate of Heat Release from Building Products (Cone Calorimeter), Genever(1993)
  8. Petrella, R.Y., The Assessment of Full-scale Fire Hazards from Cone Calorimeter Data, Journal of Fire Sciences, Vol. 12, pp.14-43(1994) https://doi.org/10.1177/073490419401200102