Advanced Protective Relaying Algorithm by Flux-Differential Current Slope Characteristic for Power Transformer

전력용 변압기용 자속-차전류 기울기 특성에 의한 개선된 보호계전 알고리즘

  • Published : 2004.07.01

Abstract

The most widely used primary protection for the internal fault detection of power transformers is current percentage differential relaying(PDR). However, the harmonic components could be decreased by magnetizing inrush when there have been changes to the material of iron core or its design methodology. The higher the capacitance of high voltage status and underground distribution, the more differential current includes the second harmonic component during occurrence of an internal fault. Therefore, the conventional harmonic restraint methods need modification. This paper proposes an advanced protective relaying algorithm by fluxt-differential current slope characteristic and trend of voltage and differential current. To evaluate the performance of proposed algorithm, we have made comparative studies of PDR fuzzy relaying, and DWT relaying. The paper is constructed power system model including power transformer, utilizing the WatATP99, and data collection is made through simulation of various internal faults and inrush. As the results of test. the new proposed algorithm was proven to be faster and more reliable.

Keywords

References

  1. 한국전력공사 전력연구원, '보호제어 유니트의 소프트웨어', 변전소종합보호제어 시스템설계 및 제작기술 개발 최종보고서 부록, pp. 1-87, 1997.2
  2. 유상봉, 임성준, 강창원, 이순형, 한찬호, 박용덕, 전명수, 이규복, 김정철 공저, '보호계전 시스템의 실무활용 기술', 도서출판 기다리, pp. 258-271, 2002.3
  3. 박철원, 권명현, 신명철, '도비시 웨이브렛변환을 이용한 변압기의 여자돌입과 내부고장 판별논리기법', 대한전기학회 논문지, 50A권 5호, pp. 211-217, May 2001
  4. C.W. Park, M.C. Shin, JH. Kim, 'Fuzzy Logic-Based Relaying for Large Power Transformer Protection', IEEE Trans. on PWRD., Vol.18, No.3, pp.718-724, July 2003 https://doi.org/10.1109/TPWRD.2003.813598
  5. 강용철, 이병은, 김은숙, 원성호, '쇄교자속비를 이용한 변압기 보호', 대한전기학회 논문지, 52A권 11호, pp. 655-660, Nov. 2003
  6. Sun Zhijie, Zeng Xianhua, Tang Hansong, et al., 'Flux Restrained Transformer Differential Protection', 2003 ACPSP, Vol.1, pp. 299-303, Oct. 2003
  7. Sang-Tae Kim, Bo-Geon Jin, Seung-Jae Lee, Sang-Hee Kang, Myeon-Song Choi, Sang-Hyun Yoon, Tae-Sung Lee, Sang-Ki Chung, 'v-i trend-based protective relaying algorithm for 3-phase power transformer', Power Engineering Society Summer Meeting, 2001. IEEE, Volume: 1, July pp. 605-610 https://doi.org/10.1109/PESS.2001.970107
  8. M.A. Rahman, B. So, M.R. Zaman and M.A. Hoque, 'Testing of Algorithms for a Stand-Alone Digital Relay for Power Transformer', IEEE Trans. on PWRD., Vol.13, No.2, pp. 374-385, April 1998 https://doi.org/10.1109/61.660904
  9. 권기백, 서희석, 신명철 'DSP의 DMA 제어기를 이용한 변압기용 디지털 보호계전기의 성능향상', 대한전기학회 논문지, 52A권 11호, pp. 647-653, Nov. 2003
  10. 박철원, 박재세, 신명철 외, '전력용 변압기를 위한 IED의 설계에 관한 연구', 2003년도 대한전기학회 하계학술대회 논문집, pp. 268-270, July 2003
  11. Alexander, R.L., 'Intelligent electronic device (IED) technology SCADA and 30 metering', Rural Electric Power Conference, 2002, pp. C6-C6_3, IEEE 2002
  12. 명지대학교 차세대전력기술센터, 'Next-Generation Protection Technology', pp. 1-214 Feb. 2002
  13. A.T. Johns, S.K. Salman, 'Digital Protection for Power System', IEEE POWER SERIES 15, Peter Peregrinus Ltd., pp. 183-187, 1995
  14. Patrick Bastard, Pierre Bertand, Michel Meunier, 'A Transformer Model for Winding Fault Studies', IEEE Trans. on PWRD., Vol.9, No.2, pp. 690-699, April 1994 https://doi.org/10.1109/61.296246
  15. 강상희, 이승재, 김일동, 김명철, 김기화, '차동전류 보호계전을 위한 변압기 특성분석', 1996년도 대한전기학회 하계학술대회 논문집, pp. 671-673, July 1996
  16. 박철원, 박재세, 신명철, '변압기 보호용 IED를 위한 개선된 알고리즘의 비교', 2003년도 대한전기학회 전력기술부문회 추계학술대회 논문집, pp. 210-212, Nov. 2003