초록
A capillary tube, which is a common expansion device in small sized refrig-eration and air-conditioning systems, should be redesigned properly to establish an optimum operation cycle of a refrigerating system with alternative refrigerants. Based on experimental data for R-22, R-290, and R-407C, an empirical correlation is developed to predict mass flow rate through capillary tubes. Dimensionless parameters are derived from the Buckingham Pi theorem, considering the effects of operating conditions and capillary tube geometry on mass flow rate. Approximately $97\%$ of the present data are correlated within a relative deviation of $\pm\;10\%.$ The present correlation also predicts the data obtained from open literature within $\pm\;15\%.$ In addition, rating charts of refrigerant flow rate for R-12, R-22, R-134a, R-152a, R-407C, R-410A, R-290, and R-600a are developed.