DC 급전시스템의 지락보호계전시스템 개발

Development of Ground Fault Protective Relaying Schemes for DC Traction Power Supply System

  • 발행 : 2005.09.01

초록

In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot Identify the faulted region which causes long traffic delays and safety problem to passengers. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. One is bus differential protective relay and the other is ground overcurrent protective relay. Both type of relays is similar in principle to the ordinary bus differential protective relay and the ground overcurrent relay used in other power system. In DC traction power supply system, since it is ungrounded, ground fault current is not big enough to operate those relays. To solve the problem, a current control device, called device 'X', is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. Algorithms for these relays are developed and their validity are verified by EMTP simulation.

키워드

참고문헌

  1. 서울도시철도공사, '전기(변전)분야실습교재', pp153-156, 1998
  2. 일본철도전화협회, 급전회로보호시스템, P9