Dynamic Characteristics Analysis of Closing Resistors of Gas Insulated Switchgear

가스절연 개폐장치 투입저항의 동특성 해석

  • Published : 2005.11.01

Abstract

GIS(Gas Insulated Switchgear) is used in electric power system, to insure non conductivity, breaking capacity and operating reliability. The commercial dynamic analysis code COSMOS MOTION and 3-D modeling program SOLID WORKS were used to simulate dynamic analysis of the closing resistors of the GIS in this paper. To reduce chatter vibration of closing resistors, the motion of moving and fixed parts of closing resistors were simulated by varying the spring constant, the damping coefficient and the mass of moving and fixed parts. The simulated results were compared with experimental results. As a result, chatter vibration of closing resistors of the GIS could be reduced by using the results. These data can be used to determine the spring constant, the damping coefficient and mass of a moving part to reduce chatter vibration when the next model is developed.

Keywords

References

  1. Chen, Fu-chen, 'Dynamic response of spring-type operating mechanism for 69kV $SF_6$ gas insulated circuit breaker,' Mechanism and Machine Theory, Vol. 38, pp. 119-134, 2003 https://doi.org/10.1016/S0094-114X(02)00095-2
  2. Lee, Y. H., Lee, H. D., Park. J. N., Shin, Y. S., Park, J. S. and Seo, J. M., 'Characteristic as a Resonance Frequency of $SF_6$ Gas,' Proceedings of the KIEE Summer Annual Meeting, pp. 112-114, 2003
  3. Lee, S. H., Min, K. S., Park, S. W., Kang, S. M., Lee, J. T., Park, K. Y., Shin, P. S. and Ko, D. S., 'Development of Gas Circuit Breaker for 1 Break of 362kV 63kA 8000A,' The Second National Symposium on Electric Power Apparatus, Materials and Their Application, pp. 120-122, 1998
  4. Kim, Y. G., Yoon, S. J., Moon, K. L. and Seo, J. M., 'Impact Analysis of Circuit Breaker by an Elastic-Plastic FEM,' Proceedings of the KIEE Autumn Annual Meeting, pp. 645-648, 1999
  5. Ochiai, I., Kohyama, H., Ito, H., Hidaka, M., Sugiyama, T., Yamamoto, H. and Matuszak, D., 'Development of 550kV 63kA one-breaker gas circuit breaker,' Transmission and Distribution Conference and Exhibition 2002 : Asia Pacific IEEE/PES, Vol. 1, pp. 93-98, 2002 https://doi.org/10.1109/TDC.2002.1178266
  6. Ahn, K. Y. and Jeong, K. Y., 'Optimization of the Spring Design Parameters of a Circuit Breaker for Satisfying Specified Dynamic Characteristics,' Journal of the KSPE, Vol. 21, No. 3, pp. 132-138, 2004
  7. Legate, A. C., Brunke, J. H., Ray, J. J. and Yasuda, E. J., 'Elimination of closing resister on EHV circuit breakers,' IEEE Transactions on Power Delivery, Vol. 3, Issue 1, pp. 223-231, 1998 https://doi.org/10.1109/61.4249