Simulation and Experimental Study on an Air-Cooled $NH_3/H_2O$ Absorption Chiller

공랭형 $NH_3/H_2O$ 흡수식 냉동기의 모사 및 실험적 연구

  • Oh Min Kyu (Graduate School, Department of Mechanical Engineering, Kyung Hee University) ;
  • Kim Hyun Jun (Graduate School, Department of Mechanical Engineering, Kyung Hee University) ;
  • Kim Sung Soo (Graduate School, Department of Mechanical Engineering, Kyung Hee University) ;
  • Kang Yong Tae (Department of Mechanical Engineering, Kyung Hee University)
  • Published : 2005.11.01

Abstract

The objective of this paper is to study the effects of the cooling air mass flow rate and the heat input variation by the simulation and the experiment. An air-cooled $NH_3/H_2O$ absorption chiller is tested in the present study. The nominal cooling capacity of the single effect machine is 17.6 kW (5.0 USRT). The overall conductance (UA) of each component, the cooling capacity, coefficient of performance and each state point are measured with the variation of the cooling air mass flow rate and the heat input. It is found that the COP and cooling capacity increase and then decreases with increasing the heat input. It is also found that the COP and the cooling capacity increase and keep constant with increasing the cooling air mass flow rate. The maximum COP is estimated as 0.51 and the optimum cooling air mass flow rate is $217\;m^3/min$ from the present experiment.

Keywords

References

  1. Priedeman, D. K., Garrabrant, M. A., Mathias, J. A., Stout, R. E. and Christensen, R. N., 1998, Performance of a Residentia-Sized GAX Absorption Chiller, ASME
  2. Jeong, S. Y, 1995, A numerical simulation of air-cooled ammonia/water GAX absorption cooling cycle, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 7, No. 3, pp. 488-501
  3. Kim, B. J., 2004, Dynamic analysis of an ammonia-water absorption chiller, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 16, No. 10, pp. 990-999
  4. Chyu, M.-C. and Bergles, A. E., 1989, Hori- zontal tube falling film evaporation' with structured surfaces, Transactions of the ASME, Journal of Heat Transfer, Vol. 111, p.524
  5. Cho, H. C., Kim, C. D., Kim, I. S., Park, C. W. and Kang, Y. T., 2002, Charactristics of absorption heat transfer on micro-scale hatched tubes with different surface roughness, Korean Journal of Air-Conditioning and Refrigeration Engineering, 14 (8), pp.641-647
  6. Kang, Y. T., Kunugi, Y. and Kashiwagi, T., 2000, Review of advanced absorption cycles: Performance improvement and temperature lift enhancement, International Journal of Refrigeration, Vol. 23, No. 5, pp.388-411 https://doi.org/10.1016/S0140-7007(99)00064-X
  7. Grossman, G. and Zaltash, A., 2001, Absimmodular simulation of advanced absorption systems, International Journal of Refrigeration, Vol. 24, pp. 531-543 https://doi.org/10.1016/S0140-7007(00)00051-7
  8. Yun, H. J., Kim, S. S., Kim, J. K. and Kang, Y. T., 2004, Performance analysis of a 5RT air-cooled $NH_3-H_2O$ absorption chiller. with. the variation of heat input, Korean Journal of Air-Conditioning and Refrigeration. Engineering, 16(5), pp.438-443