Measurement and Analysis of Surges on Information Devices Installed in a Power Substation

변전소내 정보기기에서 서지의 측정과 분석

  • 송재용 (한국해양대학교 전기전자공학부) ;
  • 박대원 (한국해양대학교 전기전자공학부) ;
  • 서황동 (한국해양대학교 전기전자공학부) ;
  • 한주섭 (한국해양대학교 전기전자공학부) ;
  • 길경석 (한국해양대학교 전기전자공학부)
  • Published : 2005.04.01

Abstract

This paper deals with the analysis results of surge voltage and current measured on information devices installed in a power substation. The power recorder to measure surge voltage and current was connected to signal lines near power transformers and switches, and the time resolution of the power recorder is 4 MS/s. Peak value of the measured surge voltage and current were ranges of 500~1,300v and 500~3,100k, respectively. During the period of measurement, over 5~10 events per day were recorded. Consequently, information devices installed in around high voltage power facilities should be designed considering the surge voltage and current caused in the condition.

본 논문은 변전소내 정보기기에 나타나는 서지전압 전류의 측정 결과에 대해 기술하였다. 서지전압 전류 관측을 위한 전력분석기는 전력용 변압기와 개폐기 주변의 신호선에 설치하였으며, 전력분석기의 시간분해능은 4 MS/s이다. 측정된 서지전압.전류의 크기는 각각 500~1,300v와 500~3,100k 이었으며, 측정기간 동안 평균 5~10회/일 이상의 서지가 기록되었다. 따라서 고전압 전력설비 주변에 설치되는 정보기기는 설치환경에 나타나는 서지의 크기를 고려하여 설계되어야 할 것이다.

Keywords

References

  1. S. B. Smith and R. B. StaSndler, 'The Effects of Surges on Electric Appliances', IEEE Trans. on Power Delivery, vol. 7, pp. 127 5-1282, 1992
  2. Bachman, L. Gullberg, F. Stricker, and H. Sachs,' An Assessment of shipboard Power Line Transients', IEEE International Symposium on Electromagnetic Compatibility, pp. 218-223, 1981
  3. 길경석, '정보통신기기용 과도이상전압의 고 속도 차단장치의 설계 및 제작', 대한전기학회 논문지, Vol. 48, No.1, pp .51-56, 1999
  4. IEC 61000-4-5, Surge immunity test, pp. 6 0-77, 1999
  5. IEEE C62.41 IEEE Recommended Protective on Surge voltages in Low-voltage AC Power Circuit, 1991
  6. KS C 0266, 산업용 설비에서의 전자파 적합성에 관한 기술지침, 1998