천장형 유닛을 설치한 교실 내의 인체 주변 온열환경에 관한 실측연구

A Field Measuring Study on the Thermal Environment of Human Surrounding in the Classroom Equipped with Ceiling Unit

  • Cho Sung-Woo (Division of Architectural Engineering, Pukyong University) ;
  • Im Young-Bin (Division of Architectural Engineering, Pukyong University) ;
  • Lee Kyung-Hee (Division of Architecture, Miryang National University)
  • 발행 : 2006.03.01

초록

This paper performed to investigate on vertical temperature distribution, effective draft temperature (ETD) and PMV (Predicted Mean Vote) in the classroom, which is located YangSan city (Kyungsangnam-Do), Korea, is equipped with ceiling unit. The vertical temperature difference between F.L+10 cm (ankle) and F.L+120 cm (neck) of a measuring point which is adjacent corridor in the classroom showed about $1^{\circ}C$ but of measuring point which is adjacent outdoor expressed up to $4^{\circ}C$, The effective draft temperature (ETD) is -2.3 and -0.52 and 0.67 at near ceiling unit but is 1.2 and 3.3 at far from ceiling unit. The PMV of total classroom showed the range of 'Cold' and 'Slightly Cold.' Therefore, to achieve comfort condition in the classroom is equipped with ceiling unit, the location of ceiling unit and discharge angle and discharge distance from ceiling unit are very important elements.

키워드

참고문헌

  1. http://sulbee.co.kr/200403/monthly/news/
  2. Noh, K. C. and Oh, M. D, 2004, Analysis on the optimal discharge angle of the 4-way air conditioner by thermal comfort and ventilation indices, SAREK Proceeding, pp.656-661
  3. Parsons, K. C., 1993, Human thermal environments (The principle and the practices), Taylor and Francis, pp. 139-150
  4. Im, M. T., 2002, Architecture environment, Bomundang, p. 89
  5. ASHRAE Fundamental, 1989, Chapter 31