지열-태양열원 복합시스템의 성능평가에 관한 연구

A Study on the Performance Evaluation of Hybrid Energy System with Geothermal and Solar Heat Sources

  • 황인주 (한국건설기술연구원 화재 및 설비연구부) ;
  • 우남섭 (성균관대학교 기계공학과 대학원) ;
  • 이홍철 (한국건설기술연구원 화재 및 설비연구부)
  • Hwang In-Ju (Fire & Engineering Services Research Dept., Korea Institute of Construction Tech) ;
  • Woo Nam-Sub (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Lee Hong-Chul (Fire & Engineering Services Research Dept., Korea Institute of Construction Tech)
  • 발행 : 2006.03.01

초록

The present study concerns the annual performance evaluation of a hybrid-renewable energy system with geothermal and solar heat sources for hot water, heating and cooling of the residential buildings. The hybrid energy system consists of ground source heat pump of 2 RT for cooling, solar collectors of $4.8m^2$, storage tank of 250 liters and gas fired backup boiler of 11.6 kW. The averaged coefficients of performance of geothermal heat pump system during cooling and heating seasons are measured as 4.1 and 3.5, respectively. Also solar fraction for hot water is measured as 35 percent. Overall, the results shows that the hybrid-renewable energy system satisfactorily operated under all climatic conditions.

키워드

참고문헌

  1. Son, B. H., Cho, C. S., Shin, H. J. and An, H. J. 2005, Cooling and heating performance evaluation of a GSHP system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No. 1, pp.71-81
  2. Choi, B. Y., Lee, S. H., Jeong, Y H. and Chai, K. H., 2003, An experimental study for heat storage type ground source heat pump system, Proceeding of the SAREK 2003 Winter, pp. 188-195
  3. Healy, P. F. and Ugursal, V. I., 1997, Performance and economic feasibility of ground source heat pumps in cold climate, International Journal of Energy Research, Vol. 21, pp.857-870 https://doi.org/10.1002/(SICI)1099-114X(199708)21:10<857::AID-ER279>3.0.CO;2-1
  4. Kaygusuz, K., 1999, Investigation of a combined solar-heat pump system for residential heating, Part 1: Experimental results, International Journal of Energy Research, Vol. 23, pp. 1213-1223 https://doi.org/10.1002/(SICI)1099-114X(199911)23:14<1213::AID-ER546>3.0.CO;2-G
  5. Axaopoulos, P., Panagakis, P. and Kyritsis, S., 1998, Experimental comparison of a solar assisted heat pump vs. a conventional. thermosyphon solar system, International Journal of Energy Research, Vol. 22, pp.1107-1120 https://doi.org/10.1002/(SICI)1099-114X(19981025)22:13<1107::AID-ER426>3.0.CO;2-E
  6. Ozgener, O. and Hepbasli, A., 2005, Experimental investigation of the performance of a solar-assisted ground-source heat pump system for greenhouse heating, International Journal of Energy Research, Vol. 29, pp. 217-231 https://doi.org/10.1002/er.1049
  7. Pahud, D. and Matthey, B., 2001, Comparison of the thermal performance of double U-type borehole heat exchangers measured in situ, Energy and Building, Vol. 33, pp. 503-507 https://doi.org/10.1016/S0378-7788(00)00106-7
  8. Kim, J H., Shin, U. Cl, Baek, N. C. and Jang, M, S., 2004, Thermal performance of solar space heating & hot water system in an apartment, Proceeding of the Korean Solar Energy Society, Spring Annual Conference, pp.98-102
  9. Hwang, I. J. and Cho, C. S., 2004, Development of effective energy utilization technology for sustainable building (II), Korea Institute of Construction Technology, pp.74-93
  10. Sanner, B., 1995, Earth heat pumps and underground thermal energy storage in Germany proceedings of the world geothermal congress, Vol. 3, Florenca, Italy, pp.1167-1172
  11. Kim, B. C., Shin, H. J and Cho, C. S., 2003, The measurement and analysis of performance of ground source heat pump system in winter, Proceeding of the SAREK, pp. 1086-1093