Simulation of a Clean Room Fire II. Needs of Smoke Control System and Springkler System

청정실 화재의 시뮬레이션 II. 제연설비와 스프링클러설비의 필요성

  • Published : 2006.06.30

Abstract

Numerical simulations were carried out for a fire in a clean room to confirm needs of a smoke control system and a sprinkler system, and to investigate a possible smoke spread-out. For a 1 MW methanol fire in a space of $39m{\times}13m$ floor and 4 m high, smoke spread-out was scrutinized for failure of the sprinkler system and/or the smoke control system. It was shown that the smoke control system removes smoke safely without the sprinkler system and that the sprinkler system is required to suppress smoke generation and spread of the fire, and to remove the smoke quickly. It was also confirmed that highly reliable sprinkler heads and automatic fire detection system are required for the sprinkler and smoke control systems.

제연설비와 스프링클러설비의 필요성을 확인하고 연기확산 가능성을 조사하기 위해 청정실 화재의 시뮬레이션을 수행하였다. 바닥면적 $39m{\times}13m$, 높이 4 m의 작업구역에 1MW의 메탄올 화재가 발생했을때, 제연설비와 스프링클러설비의 정상작동과 작동실패에 따른 연기누출 여부를 조사하였다. 제연설비가 정상적으로 작동하는 경우에는 스프링클러설비에 관계없이 연기가 안전하게 배출됨을 알 수 있었다. 화재확산과 연기발생을 억제하고 발생한 연기를 신속히 배출하기 위해 스프링클러설비가 필요하며, 스프링클러설비와 제연설비가 신속하게 작동할 수 있도록 신뢰도가 높은 스프링클러설비 헤드와 자동화재탐지설비가 필요함을 확인하였다.