An Experimental and Numerical Study on Fire Suppression Using a Mid-low Pressure Water Mist in a Carriage Fire

중저압 물분무를 이용한 객차내 화재진압에 관한 실험 및 수치해석적 연구

  • 노재성 (중앙대학교 대학원) ;
  • 양승신 (중앙대학교 대학원) ;
  • 김동현 (한국철도기술연구원 공기유동연구그룹) ;
  • 정우성 (한국철도기술연구원 공기유동연구그룹) ;
  • 장용준 (한국철도기술연구원 공기유동연구그룹) ;
  • 유홍선 (중앙대학교 기계공학부)
  • Published : 2006.06.01

Abstract

The present study investigated the effect of fire suppression using a mid-low pressure water mist in a carriage fire. The fire extinguishing time and temperature distributions below ceiling in the enclosed compartment of $2.9m{\times}2.8m{\times}5.0m$ were measured by stopwatch and k-type thermocouples for various fire positions. The numerical simulations were extensively performed using. Fire Dynamics Simulator(FDS, Ver. 4.0) code and the predictions were compared with experimental data. The prediction results showed good agreement with the measured maximum temperature in the all cases. Whereas the predicted temperature was about $40^{\circ}C$ higher than the measured one after operating of water mist. The predicted fire extinguishing times were compared with those of measured data. Fires are extinguished within 200 seconds at the experiment in Case 2 and Case 3. But in Case 1 fire was not extinguished in the numerical simulation. The reason of the discrepancy between predicted and measured data was that a simple suppression algorithm has been implemented in FDS. Also, various databases of fire properties for combustible materials and more elaborate model considering the water mist were required fur better predictions of the cooling and suffocation effect.

Keywords

References

  1. 장용준, 김동현 (2005), '철도화재 조기탐지/자동소화 장치', 한국철도기술웹진,제51호
  2. Yao, B., Fan, W. and Liao, G. (1999), 'Interaction of Water Mists with a Diffusion Flame in a Confined Space', Fire Safety Journal, Vol.33, pp.129-139 https://doi.org/10.1016/S0379-7112(99)00020-X
  3. Morita, M., Minami, T. and Kikkawa, M. (2000), 'Suppression Mechanism of Water Mist for Pool Fire', 15th Meeting of the UJNR Pannel on Fire Research and Safety, Vol.1, pp.273-279
  4. Yimin, L., Yao, B. and Qin, J. (2005), 'Preliminary Burning Tests on PVC Fires with Water Mist', Polymer Testing, Vol.24, pp.583-587 https://doi.org/10.1016/j.polymertesting.2005.02.010
  5. Kim, S, C. and Ryou, H, S. (2003), 'An Experimental and Numerical Study on Fire Suppression Using a Water Mist in an Enclosure', Building and Environment, Vol.38, pp.1309-1316 https://doi.org/10.1016/S0360-1323(03)00134-3
  6. Kim, S, C. and Ryou, H, S. (2004), 'The Effect of Water Mist on Burning Rates of Pool Fire', Journal of Fire Sciences, Vol.22, pp.305-323 https://doi.org/10.1177/0734904104041796
  7. 김성찬, 박현태, 유홍선 (2003), '물분무를 이용한 화재 제어에 관한 실험적 연구', 대한기계학회논문집, 제 27권, 제 3호, pp. 367-373
  8. 김성찬, 유홍선 (2003), '물분무에 의한 화재제어 특성에 관한 연구', 설비공학회논문집, 제 15권, 제 4호, pp.261-267
  9. 김성찬, 유홍선, 최영기, 김동현 (2005), '화재 성장 모델이 객차내 화재 특성에 미치는 영향에 관한 수치해석적 연구', 한국철도학회논문집, 제 7권, 제 3호, pp.180-185
  10. Dougal, D. (1985), 'An Introduction to Fire Dynamics', ACADEMIC PRESS, pp.152-185
  11. NIST (2004), 'Fire Dynamics Simulator (Version 4.0) - Technical Reference Guide', Fire Research Division, Building Fire Research Laboratory