Fire Resistance Performance of Load Bearing Hybrid Panel Infilled with Light-weight Formed Mortar

복합스터드에 경량기포모르터를 충전한 내력벽체의 내화성능 비교연구

  • Received : 2006.03.23
  • Published : 2007.03.30

Abstract

The purpose of this paper is to evaluate the fire resistant performances of load-bearing wall using both composite and steel stud panel infilled with light-weight formed mortar under axial loading according to KS F 2257(1999). The minimum requirement of 2 hours fire resistant rating is needed for the residential and commercial buildings under the fire regulation of Korea. From test results, it is found that two types of specimen composed of the hybrid stud and steel stud panel filled with light-weight formed mortar fited in with the requirement of 2 hours fire resisting rate for the load-bearing wall. In the conclusions, the specimen with hybrid stud shows predominating fire-resistant performance on the adiabatic effects rather than that of the steel stud specimen.

본 논문의 목적은 경량기포모르터를 충전한 스틸스터드와 복합스터드 내력벽체의 내화성능을 KS규준에 따라 평가하는데 있다. 주거용과 상업용 건물의 최소 내화 요구시간은 2시간이다. 시험 결과로부터 스틸 스터드와 복합스터드에 경량기포 모르터를 충전한 두 시험체 모두 2시간 내화 성능을 만족하는 것으로 나타났다. 또한 복합스터드 패널 시험체의 경우 내화 성능면에서 스틸 스터드 패널 시험체 보다 우수하다는 것을 정량적 평가하였다.

Keywords

References

  1. 배규웅외, "Bio 경량기포모르터를 충전하는 친환경 스틸스터드 패널형 복합화 중층건축 공법의 개발," 한국건설기술연구원, 연구보고서, 2004.
  2. 배규웅, 박금성외 3인, "벽식구조 복합화 공법개발에 따른 수평접합부의 전단성능에 관한 연구," 대한건축학회 논문집 구조계 19권 2호(통권172호), 2003, pp. 3-8.
  3. 지남용, 권인규, "스틸스터드와 석고 보드로 구성된 내력벽체의 내화성능평가," 대한건축학회 논문집 구조계 19권 8호(통권178호), 2003, pp. 83-90.
  4. 포항산업과학연구원, "스틸하우스 설계 및 시공기술교육-구조설계분야," RIST, 2000.
  5. 건설부, "프리캐스트콘크리트 조립식건축구조설계기준 및 해설", 1992.
  6. 권인규, "국내 강구조 내화구조 고찰 및 향후 발전 방향에 대한 제언," 강구조학회지 제11권 3호, 1999, 9, pp. 89-94.
  7. 건설교통부, "내화구조기준 개정연구(II)", 2000.
  8. 대한건축학회, "스틸하우스의 설계," 문운당, 2002.
  9. American Iron and Steel Institute, "Cold Formed Steel Design Manual", 2001.